Eaton DXRT 6 kVA XL

06kVA/06kW 1x1 (XL Model) UPS
Manufacturer’s declaration in accordance with IEC 62040-3
Value Proposition:
High Flexibility and Availability

High Performance
kVA=kW.
● Rack and Tower Convertible
● Form Factor 2U with <600 mm Depth.
● True Input PF 0.99
● True output Unity PF 1.
● Input THDi 3%.
● Output THDv 1%.
● Higher Power Density.
● Higher Efficiency upto 95%.
● Support Critical Virtualization.
Adjustable Battery Voltage 192 Vdc-240 Vdc.
● Adjustable Charging Current 0 A-12 Amps
● Parallel Operation upto 3 UPS’s.
● Better Short Ckt Handling Capacity.
● Auto Fault Recovery.
● Inbuilt Maintenance Bypass Switch.
● Conformal Coated Boards.
● PDU and MBS 2-in-1 kit support easy
maintenance.
● More Accessories.

High Reliability and Adaptability
Wide Input Voltage Range
● Inbuilt Hardware Current Limit Technology.
● Upgraded Phase Lock Algorithm
● Inbuilt Over-voltage Cut-off Device
● Inbuilt Over Temperature Protection.
● Upto 50 Degree Celsius operation @50%
Load (Specific to XL Model)
● Better Overload Protection upto 105%
Constant

Yes I'm Interested

UPS Specifications - DXRT6KS-IN

Category Details
Model Name DXRT6KS-IN
Catalog Name DXRT6KS-IN
Plant Part Number 9104-12897XT1
UPC Code 743172091680

INPUT

Parameter Details
Acceptable Input Voltage 110VAC-275VAC
Phase Single phase with ground
Input voltage range to take 50% load 110VAC-275VAC
Input voltage range to take 100% load 160VAC-275VAC
Inrush Current Limit 8*t rms
Input Power Factor ≥0.995
Input Frequency Range 45-55Hz / 54-66Hz (extendable to 40-70Hz when load <60%)
Input Protection Upstream breaker
Generator Set 1.5 × UPS Rating Power

OUTPUT

Parameter Details
Power (VA) max 6000
Power (W) max 6000
Power Factor 1.0
Waveform Pure sine wave
Nominal Voltage 208V/220V/230V/240V
Voltage Variation ± 1 %
Voltage Distortion ≤1% THD @ linear load
≤5% @ non-linear load

Output Frequency

Parameter Details
Synchronization Range 45-55Hz / 54-66Hz (extendable to 40-70Hz when load <60%)
Slew Rate 1 Hz/s
Battery Mode (50/60 ± 0.1) Hz

Transfer Time

Condition Time
Inverter Mode <-> Battery Mode 0ms
Battery Mode <-> Inverter Mode 0ms
Inverter Mode <-> Bypass Mode 0ms

Full Load Efficiency

Condition Efficiency
Line mode with battery full charged 95% @ 230V output with typical load
ECO Mode ≥98%

 

Overload Capability

Mode Load Condition Duration
Line Mode 100% ≤ Load ≤ 125% Constant
  105% < Load ≤ 125% 10 minutes
  125% < Load ≤ 150% 30 seconds
  Load >150% 500ms
Battery Mode 100% ≤ Load ≤ 125% Constant
  105% < Load ≤ 125% 1 minute
  125% < Load ≤ 150% 30 seconds
  Load >150% 500ms
Bypass Mode 100% ≤ Load ≤ 125% Constant
  125% < Load ≤ 150% 30 seconds
  Load >150% 500ms

BATTERY

Parameter Details
Inner Battery Rating/Type NO
External Battery Connection Connector
Back-up Time (50% load) -
Back-up Time (70% load) -
Back-up Time (Full load) 192VDC (192V-240V adjustable)
Battery Low Voltage 11.4V/pc
Battery Shutdown Voltage 10.5V/pc
Leakage Current ≤300μA
Battery Fuse Current 100A

Charger

Parameter Details
Charger Current Default 4A (1.0-12A adjustable)
Floating Voltage Phase 13.65V/pc
Charging Time -

Features

Feature Availability
ECO Mode YES
Battery Capacity Calculation YES
Fan Speed Control YES
Frequency Converter Mode (CVCF) YES, 60/50Hz
Maintenance Bypass Switch YES
Parallel Optional (up to 3 units)

INDICATOR & ALARM

Indicator/Alarm Details
Display Multi-language LCD + status LED
Battery Low Beeping every second
Battery Mode Sounding every second
Fault Continuous beeping

INTERFACE

Port/Function Availability
RS232 YES
USB YES
EPO Function YES
Comm slot Optional (NMC/Modbus/Dry Contact)
Dry Contact (Dry in/Dry out) YES
Output Connection TB
Outlet Socket TB

 

MECHANICAL

Parameter Details
WxHxD (mm) 438* 86.2* 573
Net weight (Kg) 13.1
Wheels NO

ENVIRONMENTAL

Parameter Details
Operating Temperature Range 0°C ~ 40°C (0~50°C 50% load)
Relative Humidity 0 ~ 95% (No condensing)
Audible Noise (>75% load, charger current >2A) ≤58dB
Audible Noise (75% load, charger current ≤2A or 50%~75% load, charger current >2A) ≤55dB
Audible Noise (50~75% load, charger current <2A or 25%~50% load, charger current >2A) ≤50dB
Audible Noise (25~50% load, charger current <2A or 0%~25% load) ≤48dB

REGULATIONS

Category Standard
ESD IEC 61000-4-2 Level 3
RS IEC 61000-4-3 Level 3
EFT IEC 61000-4-4 Level 3
Surge IEC 61000-4-5 Level 4
Conduction IEC 61000-4-6 Category C3
Safety IEC 62040-2 Category C3
Transportation ISTA 1A
Protection IP20 (indoor)
Performance Classification VFI-SS-111

ACCESSORIES

Item Availability
User manual Yes
Feet Yes