Eaton DXRT ( 15 & 20 ) kVA XL

The new Eaton DXRT 15K/20K UPS provides stable power for critical IT infrastructure, Industrial, Manufacturing and Medical devices. With advanced technology to improve the double conversion efficiency and reduce footprint, saving both cost and rack space. Eaton's DXRT product with it's robustness in design for hash environments. or applications outside of a comms rooms.

 

Yes I'm Interested

Technical Specifications

Specification DXRT15KPM DXRT20KPM
UPS Power Module DXRT15KPM DXRT20KPM

Physical Dimension

Specification Details
Dimension (HWD) 129mm × 438mm × 589mm
Net Weight (Kg) 23.7

Environment

Specification Details
Operating Temperature 0°C – 50°C (0-40°C no derating, 40°C – 50°C derating to 50%)
Storage Temperature -25°C – 60°C
Relative Humidity 0 – 95%
Operating Altitude 0 – 4000m (0 – 1000m no derating, 1000m – 4000m load derating 1% every 100m)
Noise Level ≤55dB
Warranty 2 years

Certification

Specification Details
Safety CE/TLC/RCM
Energy Saving CQC

EBM (External Battery Module)

Specification Details
Dimension (HWD) 129mm × 438mm × 589mm
Net Weight (Kg) 124.2

MBP (Maintenance Bypass Panel)

Specification Details
Dimension (HWD) 129mm × 438mm × 489mm
Net Weight (Kg) 21.5

 

Part Number Table

 

Product Description DXRT15K DXRT20K
UPS Power Module for ANZ DXRT15KPM AU DXRT20KPM AU
External Battery Module 480V DXRTEBM480 RT6U -
MBP Simple Version MBP20K -
MBP Standard Version MBP20KPDU -
MBP 1+1 Parallel Version MBP20K PARA -
New Network Card Network-M2 -
Modbus Card INDGW-M2 -
Environment Detection Card EMPDTH1C2 -

 

UPS Power Module Specifications

 

UPS Power Module DXRT15KPM DXRT20KPM
Input    
Rated Input Voltage 1 phase 220/230/240V; 3 phase 380/400/415V 1 phase 220/230/240V; 3 phase 380/400/415V
Input Voltage Range 160V-300V full load; 100V-160V linear derating 160V-300V full load; 100V-160V linear derating
Rated Input Frequency 50Hz/60Hz 50Hz/60Hz
Input Frequency Range 40Hz – 70Hz 40Hz – 70Hz
Input Frequency Phase Lock Range 50Hz system: 45Hz – 55Hz; 60Hz system: 54Hz – 66Hz 50Hz system: 45Hz – 55Hz; 60Hz system: 54Hz – 66Hz
System Compatibility TN-S / IT TN-S / IT
Input Power Factor (PF) >0.995 for both 1-phase and 3-phase >0.995 for both 1-phase and 3-phase
THDi ≤3% linear load; ≤5% non-linear load ≤3% linear load; ≤5% non-linear load
Output    
Input-Output Phase Connection Input-output 3-1, 3-3, 1-1 Input-output 3-1, 3-3, 1-1
Rated Output Voltage 1 phase 220/230/240V; 3 phase 380/400/415V 1 phase 220/230/240V; 3 phase 380/400/415V
Rated Output Frequency 50Hz/60Hz 50Hz/60Hz
Rated Output Apparent Power 15KVA 20KVA
Rated Output Active Power 15KW 20KW
Max PF 1 1
Voltage Variation ±1% ±1%
THDV ≤1% linear load; ≤3% non-linear load ≤1% linear load; ≤3% non-linear load
Load Crest Ratio ≥3:1 ≥3:1
Output Connection Terminal block Terminal block
Overload Capacity in Line Mode (at Rated Voltage) 105% < Load ≤125%: 10min
125% < Load ≤150%: 1min
>150%: 0.5s
105% < Load ≤125%: 10min
125% < Load ≤150%: 1min
>150%: 0.5s