06kVA/06kW 1x1 (XL Model) UPS
Manufacturer’s declaration in accordance with IEC 62040-3
Value Proposition:
High Flexibility and Availability
● kVA=kW
● True Input PF 0.99
● True output Unity PF 1
● Input THDi 3%
● Output THDv 1%
● Higher Power Density
● Higher Efficiency upto 95%
● Support Critical Virtualization
● Adjustable Battery Voltage 192 Vdc-240 Vdc.
● Adjustable Charging Current 0A-12 Amps
● Parallel Operation upto 3 UPS’s.
● Better Short Ckt Handling Capacity.
● Auto Fault Recovery.
● Inbuilt Maintenance Bypass Switch.
● Conformal Coated Boards.
● More Accessories.
| Category | Specification |
|---|---|
| Product Details | |
| Product Name | Eaton 9E-IN 6000VAXL |
| Model Name | 9E6KS-IN |
| Catalog Name | 9E6KS-IN |
| Plant Part Number | 9104-12878XT1 |
| UPC Code | 743172091758 |
| Input | |
| Acceptable Input Voltage | 110VAC-275VAC |
| Phase | Single phase with ground |
| Input Voltage Range (50% load) | 110VAC~275VAC |
| Input Voltage Range (100% load) | 160VAC~275VAC |
| Inrush Current Limit | 8*Irms |
| Input Power Factor | ≥0.995 |
| Input Frequency Range | 45-55Hz / 54-66Hz (extendable to 40~70HZ when load < 60%) |
| Input Protection | Upstream breaker |
| Generator Set | 1.5 x UPS Rating Power |
| Output | |
| Max Power (VA) | 6000 |
| Max Power (W) | 6000 |
| Power Factor | 1.0 |
| Waveform | Pure sine wave |
| Nominal Voltage | 208V/220V/230V/240V |
| Voltage Variation | ± 1% |
| Voltage Distortion | <1% THD @ linear load, <5% @ non-linear load |
| Output Frequency Synchronization | 45-55Hz / 54-66Hz (extendable to 40~70HZ when load < 60%) |
| Slew Rate | 1 Hz/s |
| Battery Mode Frequency | (50/60±0.1) Hz |
| Transfer Time | |
| Inverter Mode ↔ Battery Mode | 0ms |
| Battery Mode ↔ Inverter Mode | 0ms |
| Inverter Mode → Bypass Mode | 0ms |
| Full Load Efficiency | |
| Line Mode (Battery Full Charged) | 95% @ 230V output with typical load |
| ECO Mode | ≥98% |
| Overload Capability | |
| Line Mode | |
| 100%<Load≤105% | Constant |
| 105%<Load≤125% | 10 minutes |
| 125%<Load≤150% | 30s |
| >150% | 500ms |
| Battery Mode | |
| 100%<Load≤105% | Constant |
| 105%<Load≤125% | 1 minute |
| 125%<Load≤150% | 30s |
| >150% | 500ms |
| Bypass Mode | |
| 105%<Load≤125% | Constant |
| 125%<Load≤150% | 30s |
| Load > 150% | 500ms |
| Indicator & Alarm | |
| Display | Multi-language LCD + status LED |
| Battery Mode | Beeps every four seconds |
| Battery Low | Sounds every second |
| Overload | Sounds twice every second |
| Fault | Continuous beeping |
| Interface | |
| RS232 | Yes |
| USB | Yes |
| EPO Function | Yes |
| Comm Slot Box | Yes |
| Comm Card | Optional (NMC/Modbus/Dry Contact) |
| Dry Contact (Dry in/Dry out) | Yes |
| Input Connection | TB |
| Outlet Socket | TB |
| Mechanical | |
| Dimensions (WxHxD) | 225 × 348 × 452 mm |
| Net Weight | 13.0 kg |
| Wheels | No |
| Environmental | |
| Operating Temperature Range | 0°C ~ 40°C (40~50°C at 50% load) |
| Relative Humidity | 0 ~ 95% (Non-condensing) |
| Audible Noise (>75% load, charger >2A) | ≤55dB |
| Audible Noise (>75% load, charger <2A or 50%~75% load, charger >2A) | ≤50dB |
| Audible Noise (50%~75% load, charger <2A or 25%~50% load, charger >2A) | ≤45dB |
| Audible Noise (25%~50% load, charger <2A or 0%~25% load) | ≤40dB |
| Regulations | |
| ESD | IEC 61000-4-2 Level 3 |
| RS | IEC 61000-4-3 Level 3 |
| EFT | IEC 61000-4-4 Level 4 |
| Surge | IEC 61000-4-5 Level 4 |
| Conduction | IEC 62040-2 Category C3 |
| Radiation | IEC 62040-2 Category C3 |
| Safety | CE Marked |
| Transportation | ISTA 1H |
| Protection | IP 20 |
| Performance Classification | VFI-SS-111 |