03 kVA 1x1 (XL Model) UPS
Manufacturer’s declaration in accordance with IEC 62040-3
Value Proposition:
High Performance
High Reliability and Adaptability
High Flexibility and Availability
Major Application
| Specification | Details |
|---|---|
| Model Name | Eaton 9E-IN 3000XL |
| Catalog Number | E9E3KXL-IN |
| Plant Part Number | 9103-83888XT1 |
| UPC Code | 743172091833 |
| Specification | Details |
|---|---|
| Acceptable Input Voltage | 100VAC-300VAC |
| Phase | Single phase with ground |
| Transfer Voltage Range (50% load) | 100VAC-300VAC |
| Transfer Voltage Range (100% load) | 160VAC-300VAC |
| Line Low Loss | 160VAC/100VAC (±3%) |
| Line Low Comeback | 165VAC/105VAC (±3%) |
| Line High Loss | 300VAC (±3%) |
| Line High Comeback | 290VAC (±3%) |
| Nominal Input Current @ 230V | 11.67A |
| Inrush Current Limit | 8 * Irms |
| THDi | <9% with R full load @ 230V input |
| Input Power Factor | ≥0.99 (R FULL LOAD) @ 230V input |
| Input Frequency Range | 45-55Hz / 54-66Hz |
| Input Protection | Breaker |
| OVCD Withstand | 440VAC, 24 Hours |
| Generator Set Compatibility | 2.2 x UPS Rating Power |
| Specification | Details |
|---|---|
| Output Power (VA) max | 3000 |
| Output Power (W) max | 2400 |
| Output Power Factor | 0.8 |
| Output Waveform | Pure Sine Wave |
| Output Nominal Voltage | 200V / 208V / 220V / 230V / 240V |
| Output Voltage Variation | ±1% |
| Output Transient Recovery | 100ms (IEC 62040-3 Non-linear load) |
| Output Voltage Distortion (Line Mode) | <3% THD (linear load) |
| Output Voltage Distortion (Battery Mode) | <3% THD (linear load, 12V per battery) |
| Output Voltage Distortion (Non-Linear Load, Line Mode) | <7% THD |
| Output Voltage Distortion (Non-Linear Load, Battery Mode) | <7% THD (12V per battery) |
| Output Frequency in Inverter Mode | 45-55Hz / 54-66Hz |
| Output Frequency Slew Rate | 1 Hz/s |
| Output Frequency in Battery Mode | 50/60 ±0.05 Hz |
| Transfer Time (Inverter to Battery) | 0ms |
| Transfer Time (Inverter to Bypass) | 4ms |
| Line Mode Efficiency @ Full Load | >91% |
| ECO Mode Efficiency @ Full Load | >97.5% |
| Battery Mode Efficiency @ Full Load | >86% |
| Condition | Response Time |
|---|---|
| Line Mode | |
| 100% – 105% | Constant |
| 105% – 130% | 60s |
| 130% – 150% | 10s |
| >150% | 300ms |
| Battery Mode | |
| 100% – 105% | Constant |
| 105% – 130% | 10s |
| 130% – 150% | 1s |
| >150% | 300ms |
| >105% and Vbat <10.5V | 300ms |
| Specification | Details |
|---|---|
| DC Voltage | 96VDC |
| Battery Low Voltage (Full Load) | 89.6VDC (11.2V per battery) |
| Battery Shutdown Voltage (0-30% Load) | 88VDC (11V per battery) |
| Battery Shutdown Voltage (30-70% Load) | 84VDC (10.5V per battery) |
| Battery Shutdown Voltage (>70% Load) | 80VDC (10V per battery) |
| Charger Current | 10A (Adjustable: 2/4/6/8/10A) |
| Leakage Current | <300uA |
| Feature | Availability |
|---|---|
| ECO Mode | Yes |
| EPO Function | NA |
| Battery Capacity Calculation | Yes |
| Fan Speed Control | Yes |
| Frequency Converter Mode (CVCF) | Yes (60% load) |
| Specification | Details |
|---|---|
| RS232 | Yes |
| USB | NA |
| COM Slot | Yes |
| NMC Card | Optional |
| AS400 Card (Dry Contact) | Optional |
| Modbus Card | Optional |
| Input Connection | Input Terminal Block |
| Outlet Socket | 3 x IEC 10A outlets, 1 terminal block |
| Specification | Details |
|---|---|
| Dimensions (WxHxD) (mm) | 102 x 327 x 390 |
| Net Weight | 6.1Kg |
| Operating Temperature Range | 0°C ~ 40°C |
| Relative Humidity | 0 ~ 95% (No Condensing) |
| Audible Noise | ≤50dB at 1m |
| Standard | Compliance |
|---|---|
| ESD | IEC 61000-4-2 Level 3 |
| RS | IEC 61000-4-3 Level 3 |
| EFT | IEC 61000-4-4 Level 4 |
| Surge | IEC 61000-4-5 Level 4 |
| Safety | BIS |
| Transportation | ISTA 2A |
| Protection | IP20 (Static) |
| Standard | Details |
|---|---|
| Low Frequency Conducted Disturbances | Criteria A (IEC 61000-2-2:2002) |
| Harmonic Current | Class A (IEC 61000-3-2:2014) |
| ESD | Criteria B, Level 3 (IEC 61000-4-2:2008) |
| RS | Criteria A, Level 3 (IEC 61000-4-3:2010) |
| EFT | Criteria B, Level 4 (IEC 61000-4-4:2012) |
| Surge | Criteria B, DM Level 3: 2KV, CM Level 4: 4KV (IEC 61000-4-5:2014) |
| C/S | Criteria A, Level 3 (IEC 61000-4-6:2013) |
| M/S | Criteria B, Level 4 (IEC 61000-4-8:2009) |
| Voltage Dips & Short Interruptions | Criteria B, Level 4 (IEC 61000-4-11:2004) |
| Certification | Availability |
|---|---|
| BIS | Yes |
| CE | NA |