03 kVA 1x1 (XL Model) UPS
Manufacturer’s declaration in accordance with IEC 62040-3
Value Proposition:
High Performance
High Reliability and Adaptability
High Flexibility and Availability
Major Application
Specification | Details |
---|---|
Model Name | Eaton 9E-IN 3000XL |
Catalog Number | E9E3KXL-IN |
Plant Part Number | 9103-83888XT1 |
UPC Code | 743172091833 |
Specification | Details |
---|---|
Acceptable Input Voltage | 100VAC-300VAC |
Phase | Single phase with ground |
Transfer Voltage Range (50% load) | 100VAC-300VAC |
Transfer Voltage Range (100% load) | 160VAC-300VAC |
Line Low Loss | 160VAC/100VAC (±3%) |
Line Low Comeback | 165VAC/105VAC (±3%) |
Line High Loss | 300VAC (±3%) |
Line High Comeback | 290VAC (±3%) |
Nominal Input Current @ 230V | 11.67A |
Inrush Current Limit | 8 * Irms |
THDi | <9% with R full load @ 230V input |
Input Power Factor | ≥0.99 (R FULL LOAD) @ 230V input |
Input Frequency Range | 45-55Hz / 54-66Hz |
Input Protection | Breaker |
OVCD Withstand | 440VAC, 24 Hours |
Generator Set Compatibility | 2.2 x UPS Rating Power |
Specification | Details |
---|---|
Output Power (VA) max | 3000 |
Output Power (W) max | 2400 |
Output Power Factor | 0.8 |
Output Waveform | Pure Sine Wave |
Output Nominal Voltage | 200V / 208V / 220V / 230V / 240V |
Output Voltage Variation | ±1% |
Output Transient Recovery | 100ms (IEC 62040-3 Non-linear load) |
Output Voltage Distortion (Line Mode) | <3% THD (linear load) |
Output Voltage Distortion (Battery Mode) | <3% THD (linear load, 12V per battery) |
Output Voltage Distortion (Non-Linear Load, Line Mode) | <7% THD |
Output Voltage Distortion (Non-Linear Load, Battery Mode) | <7% THD (12V per battery) |
Output Frequency in Inverter Mode | 45-55Hz / 54-66Hz |
Output Frequency Slew Rate | 1 Hz/s |
Output Frequency in Battery Mode | 50/60 ±0.05 Hz |
Transfer Time (Inverter to Battery) | 0ms |
Transfer Time (Inverter to Bypass) | 4ms |
Line Mode Efficiency @ Full Load | >91% |
ECO Mode Efficiency @ Full Load | >97.5% |
Battery Mode Efficiency @ Full Load | >86% |
Condition | Response Time |
---|---|
Line Mode | |
100% – 105% | Constant |
105% – 130% | 60s |
130% – 150% | 10s |
>150% | 300ms |
Battery Mode | |
100% – 105% | Constant |
105% – 130% | 10s |
130% – 150% | 1s |
>150% | 300ms |
>105% and Vbat <10.5V | 300ms |
Specification | Details |
---|---|
DC Voltage | 96VDC |
Battery Low Voltage (Full Load) | 89.6VDC (11.2V per battery) |
Battery Shutdown Voltage (0-30% Load) | 88VDC (11V per battery) |
Battery Shutdown Voltage (30-70% Load) | 84VDC (10.5V per battery) |
Battery Shutdown Voltage (>70% Load) | 80VDC (10V per battery) |
Charger Current | 10A (Adjustable: 2/4/6/8/10A) |
Leakage Current | <300uA |
Feature | Availability |
---|---|
ECO Mode | Yes |
EPO Function | NA |
Battery Capacity Calculation | Yes |
Fan Speed Control | Yes |
Frequency Converter Mode (CVCF) | Yes (60% load) |
Specification | Details |
---|---|
RS232 | Yes |
USB | NA |
COM Slot | Yes |
NMC Card | Optional |
AS400 Card (Dry Contact) | Optional |
Modbus Card | Optional |
Input Connection | Input Terminal Block |
Outlet Socket | 3 x IEC 10A outlets, 1 terminal block |
Specification | Details |
---|---|
Dimensions (WxHxD) (mm) | 102 x 327 x 390 |
Net Weight | 6.1Kg |
Operating Temperature Range | 0°C ~ 40°C |
Relative Humidity | 0 ~ 95% (No Condensing) |
Audible Noise | ≤50dB at 1m |
Standard | Compliance |
---|---|
ESD | IEC 61000-4-2 Level 3 |
RS | IEC 61000-4-3 Level 3 |
EFT | IEC 61000-4-4 Level 4 |
Surge | IEC 61000-4-5 Level 4 |
Safety | BIS |
Transportation | ISTA 2A |
Protection | IP20 (Static) |
Standard | Details |
---|---|
Low Frequency Conducted Disturbances | Criteria A (IEC 61000-2-2:2002) |
Harmonic Current | Class A (IEC 61000-3-2:2014) |
ESD | Criteria B, Level 3 (IEC 61000-4-2:2008) |
RS | Criteria A, Level 3 (IEC 61000-4-3:2010) |
EFT | Criteria B, Level 4 (IEC 61000-4-4:2012) |
Surge | Criteria B, DM Level 3: 2KV, CM Level 4: 4KV (IEC 61000-4-5:2014) |
C/S | Criteria A, Level 3 (IEC 61000-4-6:2013) |
M/S | Criteria B, Level 4 (IEC 61000-4-8:2009) |
Voltage Dips & Short Interruptions | Criteria B, Level 4 (IEC 61000-4-11:2004) |
Certification | Availability |
---|---|
BIS | Yes |
CE | NA |