Eaton 93PR ( 300 - 1200 ) kVA

93PR FEATURES AND BENEFITS

  • Smaller footprint

  • Modular and Hot-Swappable

  • Silicon carbide IGBT based power converter

  • Microprocessor based advanced algorithm

  • Lithium-ion battery compatible

  • Eaton EnergyAware technology

Ideal for mission-critical applications in:

  • Data centres

  • Healthcare

  • Commercial buildings

  • Control centres

  • Process Industries

Extra Low Total Cost of Ownership

  • Compact footprint and internal redundancy design

  • Vertical scalability reduces cost and future growth risks

  • High efficiency (> 97%) in double conversion model

Hot Sync Technology

  • Eliminates single point of failure in parallel systems

  • Enhances system reliability

Cable Entry & Connectivity

  • Top and bottom cable entry

  • Built-in device and host USB

  • Alarm inputs and relay outputs

  • Supports multiple communication protocols (HTTP(S), SNMP, MODBUS, BACnet IP)

  • 7” Color touchscreen display with LED indicators

Lithium-ion Battery System

  • Advanced Battery Management System (BMS)

  • Superior energy density, long cycle life, and lower TCO

  • Seamless integration with Eaton Power Xpert UPS models

  • Wide range of runtime options (3 min to 1+ hour)

 

Yes I'm Interested

Catalog

Model 93PR-300 93PR-400 (600 kW) 93PR-600 93PR-800
Power rating (kW) 300 kW N+1 400 kW N+1 (600 kW frame capacity) 600 kW N+1 800 kW N+1
Power clustering (kW) 300 kW (5 x 60 kW) common battery 400 kW (6 x 60 kW) common battery 600 kW (10 x 60 kW) common battery 800 kW (10 x 80 kW) common battery

Frame Options

Feature 93PR-300 93PR-400 (600 kW) 93PR-600 93PR-800
Frame offering Standard input, output, MBS, bottom/top feed available, standard dust filters Standard input, output, MBS, bottom/top feed available, standard dust filters Standard input, output, MBS, bottom/top feed available, standard dust filters Standard I/O panel & cables bottom/top feed available, standard dust filters

General Characteristics

Parameter Value
Efficiency in Energy Saver System (ESS) Up to 99%
Efficiency in double conversion mode Up to 97%
Parallel capability 4 x parallel, extendable to 8 parallel, maximum 4.8 MW
Cold start Available
Sub-distribution Redundant wrap-up, compatible with generator setup in site configurable

Electrical Characteristics

Parameter Value
Voltage 380/400/415V
Voltage range 304-478V L-L / 176-276V L-N
Frequency range 40 - 70 Hz
Power factor detection 1
Harmonic distortion <1% linear load, <3% nonlinear load
Voltage THD <1% for linear load
Frequency THD <3% for nonlinear load

Battery

Parameter Value
Battery type Lithium, VRLA, Ni-Cd
Battery connection options Supports 10x common battery

Communication & Monitoring

Parameter Value
Optional accessories Communication Dry Contacts, ModBus RTU/TCP, SNMP cards, External Sync Control Bus, Top exhaust kits

Environmental Characteristics

Parameter Value
EMC standard IEC62040-2
Safety standard IEC62040-1
Protection rating IP20
Dimensions (W x D x H) 700 x 850 x 1900 mm, 2100 x 850 x 1900 mm, 2800 x 1300 x 1900 mm
Weight (kg) 376, 500, 786
Operating Temperature/Humidity 0 - 40°C, workload derating / 5-95% RH, non-condensing