Double conversion UPS
Simply effective power protection
• Double conversion provides the highest level of protection available by isolating the output power from all input anomalies.
• With a transformer-free design and sophisticated sensing and control circuitry the 93E UPS delivers an efficiency of up to 98,5%.
• Active power factor correction (PFC) provides unbeatable 0,99 input power and <5% ITHD, thus eliminating interference with other critical equipment in the same network and enhancing compatibility with generators.
• The UPS is optimized for protecting modern 0,9 p.f. rated IT equipment without the need to oversize.
True reliability
• Patented Powerware Hot Sync® technology makes possible to parallel up to 3 UPSs in capacity and up to 4 UPSs in redundancy. The technology enables load sharing without any communication line, thus eliminating single point of failure and increasing power availability.
• ABM testing and charging cycle helps you to prevent battery problems and in addition lessens corrosion prolonging battery servicelife up to 50%.
Extensive configurability
• The 93E offers over 20% smaller footprint compared to
competitive UPS offerings.
• A multilingual graphical LCD display makes possible to monitor
the UPS status easily.
• Wide software and connectivity options provide monitoring,
management and shutdown capabilities over the network.
• Connectivity options are available to suit nearly any
communication requirements, from standard serial
communications to secure remote monitoring over the Web.
Cost savings and sustainability
• A new technical platform used in Eaton´s three-phase UPS
products guarantee easy upgrades, low MTTR, similarity on
service trainings and documentation, thus lowering total cost
of ownership.
• A range of service agreement options can be easily
customized for customers’ needs and budget.
| Parameter | 80 kVA | 100 kVA | 120 kVA | 160 kVA | 200 kVA | 300 kVA | 400 kVA |
|---|---|---|---|---|---|---|---|
| UPS Output Power Rating (0.9 p.f.) | 80 | 100 | 120 | 160 | 200 | 300 | 400 |
| UPS Output Power (kW) | 72 | 90 | 108 | 144 | 180 | 270 | 360 |
| Efficiency in Double Conversion Mode (Full Load) | 94% | ||||||
| Distributed Paralleling with Hot Sync Technology | 3 + 1 | ||||||
| Inverter/Rectifier Topology | Transformer-free IGBT with PWM | ||||||
| Audible Noise | ≤55 dB (80-120 kVA), ≤70 dB (160-200 kVA), ≤73 dB (300-400 kVA) at 1m, 75% load | ||||||
| Altitude (Max) | 1000 m without derating (Max 2000 m) | ||||||
| Dimensions (W × D × H) (mm) | 600 × 800 × 1876 (80-200 kVA), 1200 × 820 × 1880 (300-400 kVA) | ||||||
| UPS Ambient Service Temperature | 0°C to +40°C |
| Parameter | Value |
|---|---|
| Input Wiring | 3 Ph + Neutral |
| Nominal Voltage Rating (Configurable) | 220/380, 230/400, 240/415 V 50/60 Hz |
| Voltage Range | +20%, -15% at 100% load, +120%, -50% at 50% load |
| Input Frequency Range | 42-70 Hz |
| Input Power Factor | 0.99 |
| Input THD | <5% |
| Soft Start Capability | Yes |
| Internal Backfeed Protection | Yes |
| Parameter | Value |
|---|---|
| Battery Type | VRLA |
| Charging Method | ABM Technology or Float |
| Battery Nominal Voltage (Lead-Acid) | 432 V (36 x 12 V, 216 Cells) |
| Charging Current / Model (A) | 10 A (80 kVA), 15 A (100 kVA), 20 A (120 kVA), 30 A (160 kVA), 40 A (200 kVA), 50 A (300 kVA), 60 A (400 kVA) |
| Parameter | Value |
|---|---|
| Output Wiring | 3 Ph + Neutral |
| Nominal Voltage Rating (Configurable) | 220/380, 230/400 (Default), 240/415 V 50/60 Hz |
| Output UTHD | <2% (100% Linear Load) |
| Output Power Factor | 0.9 |
| Permitted Load Power Factor | 0.7 Lagging – 0.9 Leading |
| Overload on Inverter | 10 min (120-125% Load), 1 min (126-150% Load), 15 s (>150% Load) |
| Overload When Bypass Available | Continuous < 115% Load, 20 ms 1000% Peak Current (Note: External bypass fuses may limit the overload capability) |
| Parameter | Value |
|---|---|
| External Battery Cabinets | Yes |
| Internal Manual Bypass Switch | Up to 120 kVA |
| External Maintenance Bypass Switch | Yes |
| MiniSlot Connectivity | Web/SNMP, ModBus/Jbus, Relay |
| Parameter | Value |
|---|---|
| MiniSlot | 2 Communication Bays |
| Serial Ports | USB, RS232 |
| Relay Inputs/Outputs | Three Signal Inputs |
| Parameter | Value |
|---|---|
| Safety (CB Certified) | IEC 62040-1 |
| EMC | IEC 62040-2, EMC Category C3 |
| Performance | IEC 62040-3 |
Buy the high-performance Eaton 93E GL (80 – 400) kVA Three Phase UPS in Noida, Delhi, and Gurugram from Feedline Power Products, your trusted three phase UPS sales & service provider in Delhi, Gurgaon & Noida NCR. Engineered for heavy-duty power backup, the Eaton 93E GL is ideal for mission-critical business applications, offering unmatched efficiency and reliability. Whether you're looking for a UPS for home in Delhi or a robust UPS for business in Noida, Feedline Power also offers the dependable Eaton 9E 2 kVA XL for smaller-scale power needs. Contact Feedline Power Products today for expert advice, reliable service, and the best deals on Eaton’s advanced UPS solutions.